MTS FlexTest® Models 40/60/100/200 Controller Hardware
Model 494.44 Two-Station System Board
FlexTest Controller Configurations
88
J23 E-Stop/Run Output Connections for the Model 494.44 System Board
The Model 494.44 System Board provides E-Stop/Program Run outputs that are
available on the J23 E-Stop/Run connector.
Cable specification To maintain EMC compliance, the J23 E-Stop/Run cable must comply with the
following specifications:
Connector type–9-pin, type D, male EMI connector.
Backshell–EMI metallized plastic or metal.
Cable–4-conductor with braided shield, with the braid connected to a metallized
plastic backshell at the chassis.
E-Stop 1 Output (NO)
HPU E-Stop = Open
494.44 System Board
J23 Estop/Run
E-Stop 2 Output (NO)
HPU E-Stop = Open
Program Run 1 Output (NO)
Program Run = Closed
Program Run 2 Output (NO)
Program Run = Closed
Reserved
J23
Estop/Run
1
2
3
4
5
6
7
8
9
Power
100-240 VAC
50-60 Hz, 1-2 A
DA Output
J24
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
LAN 2 LAN 1
DEBUG
MOTOROLA
10/100 BASE T 10/100 BASE T
SCSI
BUSY
PIB
BUSY
PCI MEZZANINE CARD
PCI MEZZANINE CARD
J55 Dig Out Dig In J54
J43A J43B
J49 Aux Pwr Estop/Run J23
Interlock
J29A J29B
Load Frame
J28 HSM A-B
HPU J25
Kommentare zu diesen Handbüchern